COMMERCIAL
Test IceMachine , check devices related to commercial
Commercial Icemachine, Walk-in Freezer Low side Pressure = [45-50 PSI] for 404A , AmericaFreezerWiring | |
Icemachine: | |
Freezers: True T-72F (3 doors)_ Evap fan blows upward, and stop blows when door open.(19PSI/237PSI with R_404A) | |
Freezers: True T-23F (1 door): Deheater=20Ω | |
Under Counter Refrigerator: R408A : low side [45_50]; R134A low side 25 psi, 1HP/1PH compressor => 8.5Amps | |
TrueŽ MFG - Defrost Time Clock: Time indicator with a "Time" sign (what time now) adjust by turning center knob ccw, the screws on circle is time to defrost. |
|
True Cooler Compressor Wiring . | |
True Beer Cooler (Mod TD-65-24 11 Oz of) R 134 low side [18_23 psi] | |
Walk-In Cooler R22: low side [45-50 or Super heat [12 to 14] or 40F-26F=14F for TXV], | |
Walk-In Freezer 404A: Low side [43 Psi ], TXV EFSE-1/2-ZP for R404A , Def Timer = pin/25 mns * 3. condenser 3 phase 240v <=> inside 240v for all loads. And if High side is so high that compressor locks out, coil solenoid should be checked. Fill freon until TXV clears | |
AC system: R410 (when open door low side 150 PSI , high side 550 PSI ) | |
TXV adjustment | |